IIR document

Experimental investigation of the effects of airflow nonuniformity on performance of a fin-and-tube heat exchanger.

Author(s) : BLECICH P.

Type of article: Article, IJR article

Summary

The effects of airflow nonuniformity on the thermal–hydraulic performance of a fin-and-tube heat exchanger were investigated experimentally. The test subject was a four-depth-row fin-and-tube heat exchanger with face split tube circuitry. Nonuniform inlet air distribution was generated by partially blocking the heat exchanger entrance cross-section. It was found that airflow nonuniformity causes thermal effectiveness deterioration and pressure drop increase. The size of effectiveness deterioration and pressure drop increase depend on the degree of airflow nonuniformity as well as on the orientation between airflow nonuniformity and tube-side fluid circuitry. For most of the observed nonuniform airflow profiles, which had low or moderate degrees of airflow nonuniformity, the effectiveness deterioration was between 5% and 10%, while the pressure drop increase was between 10% and 20%. For severely nonuniform airflow profiles the effectiveness deterioration was up to 30% and the pressure drop increase was up to 90%.

Available documents

Format PDF

Pages: 65-74

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental investigation of the effects of airflow nonuniformity on performance of a fin-and-tube heat exchanger.
  • Record ID : 30016270
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 59
  • Publication date: 2015/11

Links


See other articles in this issue (27)
See the source