IIR document

Experimental pure fluid and binary mixture performance in a heat pump equipped with a distillation column.

Author(s) : GEBBIE J. G., JENSEN M. K., DOMANSKI P. A., et al.

Type of article: Article, IJR article

Summary

An experimental heat pump system that included a distillation column, accumulator/sump, and heater was experimentally investigated using two different working fluids, R32 and a mixture of R32/R134a. Performance variations with changes in sump heater power, condenser and evaporator heat transfer fluid flow, and compressor speed were examined. Heating capacity generally increased with increases in the factors tested. Heating capacity increases were generally smaller with the R32/R134a tests than with the R32 tests, except with variations in sump heater power. An increase in sump heater power caused a pronounced increase in the circulating R32 concentration during the mixture tests, and the heating capacity increased markedly. The increase in heating capacity with sump heater power during the R32/R134a tests was on par with the increase with compressor power during these same tests. The increase in capacity with sump heater power during the R32/R134a tests also was substantial even when compared with the capacity increase with compressor speed during the R32 tests.

Available documents

Format PDF

Pages: 940-947

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental pure fluid and binary mixture performance in a heat pump equipped with a distillation column.
  • Record ID : 2005-0570
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 8
  • Publication date: 2004/12

Links


See other articles in this issue (21)
See the source