IIR document

Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement.

Author(s) : MOTA BABILONI A., NAVARRO-ESBRÍ J., BARRAGÁN-CERVERA A., et al.

Type of article: Article, IJR article

Summary

This work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a.

Available documents

Format PDF

Pages: 52-58

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement.
  • Record ID : 30013499
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 51
  • Publication date: 2015/03