IIR document

Experimental assessment of R134a and its lower GWP alternative R513A.

Author(s) : MOTA BABILONI A., MAKHNATCH P., KHODABANDEH R., et al.

Type of article: Article, IJR article

Summary

Lower GWP refrigerants are essential to mitigate the impact of refrigeration systems on climate change. HFO/HFC mixtures are currently considered to replace HFCs in refrigeration and air conditioning systems. The aim of this paper is to present the main operating and performance differences between R513A (GWP of 573) and R134a (GWP of 1300), the most used refrigerants for medium evaporation temperature refrigeration systems and mobile air conditioners. To perform the experimental comparison, 36 tests are carried out with each refrigerant at evaporating temperatures between - 15 and 12.5°C and condensing temperatures between 25 and 35°C. The conclusion of the experimental comparison is that R513A can substitute R134a with only a thermostatic expansion valve adjustment, achieving better performance and higher cooling capacity. The discharge temperature of R513A is always lower than that of R134a.

Available documents

Format PDF

Pages: 680-686

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental assessment of R134a and its lower GWP alternative R513A.
  • Record ID : 30020600
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 74
  • Publication date: 2017/02

Links


See other articles in this issue (56)
See the source