Summary
During the electricity defrosting of air cooler, some issues would arise, such as that temperature field would be damaged, energy would be lost , the refrigeration load would be increased, so a set of electric isolation device was designed. At the typical operating condition that cold storage temperature is -18°C, electric defrosting of air cooler was studied after using the partition device. Then the questions that how the partition board to influence the cold storage temperature, the temperature field around the air-cooler and the consumption of electric heating defrosting was studied through comparing the experimental data whether the defrosting partition device was used or not.The results indicate that after using the partition device, the variation of cold storage temperature is reduced, the maximum change is decreased by 5°C; ambient temperature uniformity around the air cooler is improved, the maximum change is increased by 10°C; defrosting energy consumption is reduced by 1/3. So the energy utilization rate for electricity defrosting was improved when partition board was applied.
Available documents
Format PDF
Pages: 81-84, 95
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: [In Chinese. / En chinois.]
- Record ID : 30020645
- Languages: Chinese
- Source: Journal of Refrigeration - vol. 35 - n. 160
- Publication date: 2014/12
Links
See other articles in this issue (11)
See the source
Indexing
-
Desescarche: tipos, circuitos y componentes. 1.
- Author(s) : SANZ del CASTILLO F.
- Date : 2005/12
- Languages : Spanish
- Source: Instalador - n. 425
View record
-
Effectieve ontdooiing als voorwaarde voor lucht...
- Author(s) : ZWUESTE R.
- Date : 2000/06
- Languages : Dutch
- Source: Koude & Luchtbehandeling - vol. 93 - n. 6
View record
-
DEFROSTING OF AIR COOLERS.
- Author(s) : KAKOL M., ZAKRZEWSKI B.
- Date : 1981
- Languages : Polish
- Source: Chlodnictwo - vol. 16 - n. 9-10
View record
-
Unfavourable frost: what is it, when does it oc...
- Author(s) : CLELAND D.
- Date : 2004/08
- Languages : English
- Source: EcoLibrium - vol. 3 - n. 7
View record
-
SELF-OPERATED DEFROSTERS FOR INDUSTRIAL AIR COO...
- Author(s) : KAKOL M., ZAKRZEWSKI B.
- Date : 1982
- Languages : Polish
- Source: Chlodnictwo - vol. 17 - n. 7
View record