Summary
This article presents a fault-tolerant supervisory control strategy for building condenser cooling water systems. The proposed strategy mainly consists of a model-based predictive control (MPC) scheme, a fault detection and diagnosis (FDD) scheme and a fault accommodation and tolerant (FAT) scheme. The MPC scheme using systematic optimization is employed to identify optimal control settings for the local process controllers. The FDD scheme is utilized to detect and diagnose major possible faults that may happen in the routine operation of condenser cooling water systems. The faults considered mainly include critical sensor faults, physical component performance degradations, and malfunctions of control logics. According to the types of faults that happen, the FAT scheme is then used to handle the faults in order to regain the control as far as possible. The performance of this strategy is tested and evaluated in a simulated virtual system representing the actual condenser cooling water system in a super high-rise building. The results show that the proposed strategy is capable of maintaining acceptable control performance and can help save about 0.18–5.23% total energy of the chillers and cooling towers when the operation of condenser cooling water systems suffers from some faults, as compared to that using the same control strategy but without using the FAT scheme.
Details
- Original title: Fault-tolerant supervisory control of building condenser cooling water systems for energy efficiency.
- Record ID : 30003585
- Languages: English
- Source: HVAC&R Research - vol. 18 - n. 1-2
- Publication date: 2012/02
- DOI: http://dx.doi.org/10.1080/10789669.2011.568320
Links
- External links:
See other articles in this issue (4)
See the source
-
Exergy analysis of the chiller plant with preco...
- Author(s) : XIE A., JIANG X.
- Date : 2012/06
- Languages : Chinese
- Source: Refrigeration - vol. 31 - n. 2
View record
-
COOLING TOWER ENERGY. CONSIDERATIONS FOR THE OP...
- Author(s) : HENSLEY J. C.
- Date : 1981/10
- Languages : English
- Source: Heat. Pip. Air Cond. - vol. 53 - n. 10
View record
-
INVESTIGATION OF CONTROL ALTERNATIVES FOR A STE...
- Author(s) : KLEIN S. A., NUGENT D. R., MITCHELL J. W.
- Date : 1988
- Languages : English
View record
-
Self-optimizing control of cooling tower for ef...
- Author(s) : LI X., LI Y., SEEM J. E., et al.
- Date : 2012/07/16
- Languages : English
- Source: 2012 Purdue Conferences. 2nd International High Performance Buildings Conference at Purdue.
- Formats : PDF
View record
-
Energy efficiency control strategy for air cond...
- Author(s) : YANG L., LU J., TANG H., et al.
- Date : 2013/04
- Languages : Chinese
- Source: HV & AC - vol. 43 - n. 276
- Formats : PDF
View record