Summary
Test results discussed are relative to 15 coil prototypes, having the same tube and fin geometry (25 x 21.65 mm staggered 5/8" tube banks, 2 mm fin spacing) but different fin surface geometry, from flat to wavy to louvered to "winglet". Different rates of heat transfer and pressure loss enhancement were obtained, also depending on the quality of the pressing process. General approaches to evaluate the positive features of one fin design with respect to another one provided questionable results: pressure loss influence on the air flow cannot be properly evaluated unless the actual fan head curve and the coil dimensions (front area and rows number) are stipulated.
Details
- Original title: Scambiatori ad aletta continua.
- Record ID : 2003-0139
- Languages: Italian
- Source: Industria italiana del Freddo - vol. 56 - n. 2
- Publication date: 2002/04
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (2)
See the source
-
Product-optimalisatie, een noodzakelijk kwaad?
- Author(s) : KARSTEN H.
- Date : 1997/11
- Languages : Dutch
- Source: Koude & Luchtbehandeling - vol. 90 - n. 11
View record
-
Heat exchangers for air conditioners.
- Author(s) : SHIKAZONO N.
- Date : 2000/09
- Languages : Japanese
- Source: Refrigeration - vol. 75 - n. 875
View record
-
Serpentines de enfriamiento y deshumidificacion.
- Author(s) : GARCÍA N. O.
- Date : 1999/04
- Languages : Spanish
- Source: Téc. Frio - vol. 48 - n. 513
View record
-
An experimental study of the air-side particula...
- Author(s) : AHN Y. C., KIM G. T., HWANG Y. J., et al.
- Date : 2006/05/21
- Languages : English
- Source: ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
View record
-
Nieuwe koudemiddelverdeler.
- Author(s) : MERLO U.
- Date : 2002/07
- Languages : Dutch
- Source: Koude & Luchtbehandeling - vol. 95 - n. 7
View record