Summary

Optimal louver fins suitable for 5 mm diameter tubes are designed by Computational Fluid Dynamic-based method in this study. Based on the design result, a set of fin-and-tube heat exchangers with 5 mm diameter tubes are tested to develop correlations to predict the performance of new fin-and-tube heat exchanger. According to the experimental results, it is found that water bridge occurs at the bottom of fin with hydrophilic coating, which did not occur in fin-and-tube heat exchangers with 7 mm or 10.33 mm diameter tubes in previous studies. Based on the data, correlation of j is developed to predict the heat transfer rate of fin-and-tube heat exchanger with 5 mm diameter tubes. The mean deviations of the proposed j correlation are 6.5%.