Impact of solar heat gain on radiant floor cooling system design.
Number: pap. 603
Author(s) : FENG J., SCHIAVON S., BAUMAN F.
Summary
Radiant floor cooling systems are increasingly being used in transition spaces with large glazed surfaces, such as atria, airports, and perimeter areas. For these cases, the cooling capacity can increase significantly according to the scientific literature. However, current design standards and test methods provide only limited guidance on sizing of radiant floor cooling systems and their associated air systems in the presence of solar radiation. The goals of this study are to 1) review current radiant surface cooling capacity estimation approaches; and 2) evaluate the impact of solar heat gain on radiant floor cooling capacity. Sensitivity simulation studies were conducted to investigate the influence of window-to-wall ratio, orientation, building aspect ratio, shading options, and floor material shortwave absorptivity. Review of current radiant system design standards showed that existing radiant cooling capacity estimation methods are insufficient when the system is exposed to solar radiation because shortwave radiation generated by lighting and solar are not considered. Radiant cooling capacity ratio (RCCR), defined as the ratio of the EnergyPlus simulated radiant cooling capacity to the values calculated using ASHRAE Handbooks (2012) and ISO 11855 (2012) methods, were reported to gauge the impact of solar radiation. The simulation results showed that 1) the median of the RCCRISO is 1.7 and 1.3 for RCCRASHRAE, and the enhancement is attributed to shortwave radiation (both direct and diffuse) absorption; 2) RCCR is most sensitive to shading options and slightly sensitive to shortwave absorptivity of the floor surface material.
Available documents
Format PDF
Pages: 11 p.
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Impact of solar heat gain on radiant floor cooling system design.
- Record ID : 30009392
- Languages: English
- Source: Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Publication date: 2013/06/16
Links
See other articles from the proceedings (424)
See the conference proceedings
Indexing
- Themes: Comfort air conditioning
- Keywords: Standardization; Radiation; Design; Cooling; Solar radiation; Ground; Air conditioning
-
Free subcooling with the sky: Improving the eff...
- Author(s) : GOLDSTEIN E., NASUTA D., LI S., et al.
- Date : 2018/07/09
- Languages : English
- Source: 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Thermally Active Floors. 1.
- Author(s) : NALL D. H.
- Date : 2013/01
- Languages : English
- Source: ASHRAE Journal - vol. 55 - n. 1
View record
-
Anticipating an efficient relative humidity in ...
- Author(s) : NAJAFI N. Z., HAGHIGHI A. P.
- Date : 2019/02
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 98
- Formats : PDF
View record
-
Optimizing a design for a cooling or insulating...
- Author(s) : FÄLT M., PETTERSSON F., ZEVENHOVEN R.
- Date : 2013/06/16
- Languages : English
- Source: Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Formats : PDF
View record
-
Radiant heating and cooling systems. 1.
- Author(s) : KIM K. W., OLESEN B. W.
- Date : 2015/02
- Languages : English
- Source: ASHRAE Journal - vol. 57 - n. 2
View record