IIR document

Improvement of 100W class room temperature magnetic refrigerator.

Author(s) : OKAMURA T., RACHI R., HIRANO N., et al.

Summary

A rotating magnet type magnetic refrigerator was modified and its performance has been improved. The performance of the previous magnetic refrigerator was presented at the 1st IIR International Conference on Magnetic Refrigeration at Room Temperature in 2005. The system configuration was not changed but some components were modified. The new refrigerator produces a maximum cooling power of 540 W and COP of 1.8 when the temperature at the hot end of the AMR duct is 21°C and the temperature span was 0.2°C.

Available documents

Format PDF

Pages: 2007-1

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Improvement of 100W class room temperature magnetic refrigerator.
  • Record ID : 2007-1556
  • Languages: English
  • Source: 2nd International Conference on Magnetic Refrigeration at Room Temperature
  • Publication date: 2007/04/11

Links


See other articles from the proceedings (48)
See the conference proceedings