Summary
Indoor thermal environment is important as it affects the health and productivity of building occupants. Direct expansion (DX) air-conditioning (A/C) units are commonly used for environmental control in small- to medium-scaled buildings. This paper reports on an experimental study to investigate the indoor thermal comfort characteristics under the control of a DX A/C unit having variable-speed compressor and supply fan at a fixed space cooling load but having three different ratios between its sensible part and latent part. The experimental results suggested that under a fixed indoor total cooling load with three different space sensible heat ratios of 0.92, 0.72 and 0.62, varying both speeds of compressor and supply fan in the DX A/C unit would influence indoor thermal comfort. Furthermore, when a DX A/C unit having variable-speed compressor and supply fan is used for indoor thermal comfort control under abnormal indoor load conditions, its ability of indoor thermal comfort control through varying compressor speed and supply fan speed may be duly restricted. [Reprinted with permission from Elsevier. Copyright, 2008].
Details
- Original title: Indoor thermal comfort characteristics under the control of a direct expansion air-conditioning unit having a variable-speed compressor and a supply air fan.
- Record ID : 2009-2132
- Languages: English
- Source: Applied Thermal Engineering - vol. 29 - n. 11-12
- Publication date: 2009/08
- DOI: http://dx.doi.org/10.1016/j.applthermaleng.2008.10.011
Links
See other articles in this issue (12)
See the source
Indexing
-
Displacement ventilation in non-industrial prem...
- Date : 2006/06
- Languages : English
- Source: REHVA Journal - n. 2
View record
-
Improving degree of superheat control in a dire...
- Author(s) : QI Q., DENG S., XU X., et al.
- Date : 2010/01
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 1
- Formats : PDF
View record
-
Thermal comfort and indoor air quality in rooms...
- Author(s) : LI R., SEKHAR S. C., MELIKOV A. K.
- Date : 2011/10
- Languages : English
- Source: HVAC&R Research - vol. 17 - n. 5
View record
-
Air quality in a simulated office environment a...
- Author(s) : WARGOCKI P., BAKO-BIRO Z., CLAUSEN G., et al.
- Date : 2002
- Languages : English
- Source: Energy Build. - vol. 34 - n. 8
View record
-
Does HVAC work?
- Author(s) : ROWE D.
- Date : 1996/09
- Languages : English
- Source: Archit. Sci. Rev. - vol. 39 - n. 3
View record