INFLUENCE OF TURBULENCE ON PERFORMANCE OF CIRCULAR HELICALLY FINNED TUBES.

Author(s) : FOURIE J. G., KROGER D. G.

Summary

THE PAPER DEALS WITH AN INVESTIGATION OF THE EFFECT OF VARYING CHARACTERISTICS OF THE PRESSURE GRADIENT AND HEAT TRANSFER IN FINNED TUBE EXCHANGERS (HELICAL FINS). SCREENS CONSISTING OF WIRE MESHES OR BAR GRIDS ARE INSTALLED AT DIFFERENT LOCATIONS AHEAD OF THE BUNDLES IN ORDER TO CREATE MAXIMUM TURBULENCE LEVELS OF 25%. THE TUBES ARE STAGGERED INCLUDING BUNDLES OF 1 TO 8 ROWS. FREE FLOW RATE RANGES BETWEEN 2 AND 10 M/S. WHEN THE SCREENS ARE LOCATED RELATIVELY NEAR THE BUNDLES, AT HIGH TURBULENT FREE FLOW RATES, THE EFFECTIVE HEAT TRANSFER COEFFICIENT IS INCREASED MARKEDLY, MAINLY IN THE FIRST TUBE ROW. A SIGNIFICANT CHANGE IN THE PRESSURE GRADIENT IS OBSERVED WHEN THE BAR GRID IS POSITIONED AHEAD OF A SINGLE ROW BUNDLE.

Available documents

Format PDF

Pages: vol. B-E

This document is to be digitised and will be available within 10 working days

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: INFLUENCE OF TURBULENCE ON PERFORMANCE OF CIRCULAR HELICALLY FINNED TUBES.
  • Record ID : 1988-1796
  • Languages: English
  • Source: Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.
  • Publication date: 1987/08/24
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (509)