Summary
In order to investigate the fouling of enhanced tubes, a continuous fouling test on eight enhanced tubes and one plain tube was conducted for 98 days, using a medium fouling potential water as the test water at a water velocity of ~1.6 m/s. Four periods were defined for fouling development based on the test data in this work: introduction period, initial deposit period, rapid deposit period, and stabilization period. The rank of asymptotic fouling resistance of nine test tubes was as follows: Tubes 9 > 7 > 6 > 5 > 1 > 3 > 4 > 2 > 8. The pressure drops of the nine tubes increased by 0.1 kPa to 1.32 kPa due to fouling deposit at the end of the fouling test. A fouling resistance prediction model was developed, which had a maximum error of 0.0645 for predicting the fouling resistance ratio.
Available documents
Format PDF
Pages: 9-18
Available
Public price
10 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Investigation on fouling of enhanced tubes used in a cooling tower water system based on a long-term test.
- Record ID : 30026559
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 104
- Publication date: 2019/08
- DOI: http://dx.doi.org/10.1016/j.ijrefrig.2019.05.003
Links
See other articles in this issue (50)
See the source