Measurement and analysis of vitiation of secondary air in air distribution systems.
Author(s) : YUILL D. P., YUILL G. K., COWARD A. H.
Type of article: Article
Summary
Appendix A of ANSI/ASHRAE Standard 62.1-2007, ventilation for acceptable indoor air quality, describes the recycling of unvitiated ventilation air in a recirculating air-handling system. Equation A-2 considers air delivered through the primary air path (central air distribution system) and secondary air paths, such as fan-powered boxes or transfer-air fans. It contains a variable, E(r), that describes the extent to which the secondary air comes from the zone in question, as opposed to coming from "average system return air." This paper describes the development of an equation that can be used to quantify E(r), and shows the results of the first experimental measurements of E(r). For these measurements, tracer gas experiments were carried out on an office building in Omaha, Nebraska. The study showed that the theoretical range of Er is from zero to infinity. Its range in the test building is from 0.74 to 1.01 as built, but could range from 0.14 to 1.13 if the fan-powered boxes had been located in different, but realistic, locations. These findings contradict the standard, which defines E(r) as ranging from 0 to 1.
Details
- Original title: Measurement and analysis of vitiation of secondary air in air distribution systems.
- Record ID : 2008-2208
- Languages: English
- Source: HVAC&R Research - vol. 14 - n. 3
- Publication date: 2008/05
Links
See other articles in this issue (7)
See the source
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Contamination; Calculation; Measurement; Ventilation; Flow rate; Air conditioning; Air distribution
-
Airflow and air temperature distribution in the...
- Author(s) : CHAO C. Y. H., WAN M. P.
- Date : 2004/07
- Languages : English
- Source: Build. Environ. - vol. 39 - n. 7
View record
-
The use of rotating vane anemometers to measure...
- Author(s) : SAUNDERS J., JOHNSON A., FLETCHER B.
- Date : 2000/06/04
- Languages : English
- Source: Progress in modern ventilation. Ventilation 2000. Proceedings of the 6th International symposium on ventilation for contaminant control.
View record
-
Ventilation and air quality in an office building.
- Author(s) : CHEONG K. W.
- Date : 1996
- Languages : English
- Source: Build. Serv. Eng. Res. Technol. - vol. 17 - n. 4
View record
-
Damper authority estimation and adaptive flow c...
- Author(s) : FEDERSPIEL C. C.
- Date : 1997/08
- Languages : English
- Source: CLIMA 2000, Brussels 1997, August 30 to September 2, Congress Palace.
View record
-
Mediciones para la determinación de la eficienc...
- Author(s) : JUNCÀ M.
- Date : 2009/09
- Languages : Spanish
- Source: Frío Calor Aire acondicionado - vol. 37 - n. 417
- Formats : PDF
View record