Numerical simulation of a closed wet cooling tower with novel design.

Author(s) : XIA Z. Z., CHEN C. J., WANG R. Z.

Type of article: Article

Summary

A closed wet cooling tower with novel design was proposed and numerically investigated. The studied cooling tower consists of two main parts: one heat and mass transfer unit (HMTU) and one heat transfer unit (HTU). In the HMTU, copper tubes are arranged as heat transfer tubes while plastic tubes are collocated to enlarge the mass transfer area between the spray water and the airflow. In the HTU, only copper tubes are adopted as heat transfer tubes. Heat and mass transfer process takes place among the process water, airflow and spray water in the HMTU, while in the HTU only heat transfer between the process water and the spray water is observed. A transient one dimensional distributed-parameter model was adopted to evaluate the cooling tower performance under different operating conditions. Determination of heat and mass transfer coefficients, as well as the influence of Lewis number on the cooling tower performance, was presented. [Reprinted with permission from Elsevier. Copyright, 2011.]

Details

  • Original title: Numerical simulation of a closed wet cooling tower with novel design.
  • Record ID : 30001817
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 54 - n. 11-12
  • Publication date: 2011/05
  • DOI: http://dx.doi.org/10.1016/j.ijheatmasstransfer.2011.02.025

Links


See other articles in this issue (8)
See the source