ON THE DESIGN OF RECIRCULATED-LIQUID GAS COOLER/HUMIDIFIERS.

Author(s) : LARSON R. S.

Type of article: Article

Summary

IT IS SHOWN THAT THE STANDARD DESIGN EQUATIONS FOR THE PACKED HEIGHT Z OF A COUNTERCURRENT CONTINUOUS CONTACT GAS COOLER/HUMIDIFIER WITH RECIRCULATED LIQUID ARE INCONSISTENT UNLESS THE PSYCHROMETRIC RATIO RIS EQUAL TO UNITY. THE DIFFICULTY IS TRACED TO THE COMMONLY USED BUT GENERALLY INCORRECT ASSUMPTION THAT THE LIQUID TEMPERATURE T IS UNIFORM. THE NUMERICAL SOLUTION OF THE RIGOROUS DIFFERENTIAL MASS AND ENERGY BALANCES SHOWS THAT T PASSES THROUGH A MAXIMUM IF RIS LOWER THAN 1 AND A MINIMUM IF RIS HIGHER THAN 1 ; IN CONSEQUENCE, THE STANDARD DESIGN EQUATIONS GIVE VALUES OF Z WHICH BRACKET THE EXACT RESULT.

Details

  • Original title: ON THE DESIGN OF RECIRCULATED-LIQUID GAS COOLER/HUMIDIFIERS.
  • Record ID : 1986-0581
  • Languages: English
  • Source: Ind. Eng. Chem. (Process Des. Dev.) - vol. 24 - n. 4
  • Publication date: 1985
  • Document available for consultation in the library of the IIR headquarters only.