Summary
WITH REFERENCE TO THE THERMAL CHARACTERISTICS OF BOTH COUNTERFLOW AND CROSSFLOW COOLING TOWERS, NUMEROUS COMPUTER CALCULATIONS, MADE ON THE BASIS OF THE ENTHALPY POTENTIAL THEORY COVER A RANGE OF TOTAL PRESSURES FROM 101. 3 TO 80 KPASCAL, INLET WATER TEMPERATURES FROM 303 TO 323 K (30 TO 50 DEG C), INLET WET-BULB TEMPERATURES FROM 278 TO 300 K (5 TO 27 DEG C), WATER-TO-AIR FLOW RATIOS FROM 0.5 TO 2.5. THE CTI METHOD IS CONFIRMED TO GIVE ALMOST EXACT VALUES OF COUNTERFLOW. THEN, COMPARING THE ALMOST EXACT VALUES OF CROSSFLOW CALCULATED BY A FINITE DIFFERENCE METHOD, A NEW CORRECTION FACTOR FOR CROSSFLOW TOWERS IS INTRODUCED IN THE FORM OF AN EQUATION.
Details
- Original title: [In Japanese. / En japonais.]
- Record ID : 1984-0540
- Languages: Japanese
- Source: Refrigeration - vol. 58 - n. 668
- Publication date: 1983
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (1)
See the source
-
A GENERAL THEORY OF WET SURFACE HEAT EXCHANGERS...
- Author(s) : MACLAINE-CROSS I. L., BANKS P. J.
- Date : 1981/08
- Languages : English
- Source: J. Heat Transf. - vol. 103 - n. 3
View record
-
ANALYSIS OF MECHANICAL-DRAUGHT COUNTERFLOW AIR/...
- Author(s) : SUTHERLAND J. W.
- Date : 1983/08
- Languages : English
- Source: J. Heat Transf. - vol. 105 - n. 3
View record
-
Performance of counterflow cooling towers with ...
- Author(s) : KRANC S. C.
- Date : 1993
- Languages : English
- Source: Numer. Heat Transf., A - vol. 23 - n. 1
View record
-
USE OF POCKET COMPUTERS PROGRAMMED FOR DESIGNIN...
- Author(s) : DIRKSE R. J. A.
- Date : 1983/11
- Languages : German
- Source: Kälte + Klimatechnik (Die) - vol. 36 - n. 11
View record
-
Crossflow cooling tower performance calculations.
- Author(s) : FULKERSON R.
- Date : 2009/01
- Languages : English
- Source: CTI J. - vol. 30 - n. 1
View record