ANALYSIS OF MECHANICAL-DRAUGHT COUNTERFLOW AIR/WATER COOLING TOWERS.

Author(s) : SUTHERLAND J. W.

Type of article: Article

Summary

THIS PAPER COMPARES AN ACCURATE ANALYSIS OF COUNTERFLOW COOLING TOWERS, INCLUDING WATER LOSS BY EVAPORATION, WITH THE APPROXIMATE METHOD BASED ON ENTHALPY DRIVING FORCE DEVELOPED BY MERKEL. SUBSTANTIAL UNDERESTIMATES OF TOWER VOLUME OF FROM 5 TO 15 PERCENT ARE OBTAINED WHEN THE APPROXIMATE ANALYSIS IS USED, INDICATING THE POSSIBILITY OF QUITE SERIOUS CONSEQUENCES AS FAR AS COOLING TOWER DESIGN IS CONCERNED.

Details

  • Original title: ANALYSIS OF MECHANICAL-DRAUGHT COUNTERFLOW AIR/WATER COOLING TOWERS.
  • Record ID : 1984-1852
  • Languages: English
  • Source: J. Heat Transf. - vol. 105 - n. 3
  • Publication date: 1983/08
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (11)
See the source