Optimum setpoint of condensing temperature for air-cooled chillers.

Author(s) : CHAN K. T., YU F. W.

Type of article: Article

Summary

Under head pressure control, air-cooled chillers appear inefficient because the condensing temperature is kept high; it is essential to explore how to optimize the condensing temperature to improve their efficiency. With the simulation program TRNSYS, a chiller model is developed and experimentally verified to ascertain all parameters within the chiller components. An algorithm, which can be used to determine the number of staged condenser fans by a setpoint of condensing temperature, is first introduced. The model with this algorithm serves to illustrate the extent of decrease in the condensing temperature, which has rarely been studied. When the setpoint of condensing temperature varies linearly with outdoor temperature, maximum chiller efficiency is obtained. The condensing temperature also becomes controllable, resulting in less fluctuation in chiller efficiency in different operating conditions.

Details

  • Original title: Optimum setpoint of condensing temperature for air-cooled chillers.
  • Record ID : 2004-2939
  • Languages: English
  • Source: HVAC&R Research - vol. 10 - n. 2
  • Publication date: 2004/04
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (5)
See the source