Pool boiling of R22, R124 and R134a on a plain tube.

Author(s) : CHIOU C. B., LU D. C., WANG C. C.

Type of article: Article

Summary

Experiments are conducted at saturation temperatures of 4.4 and 26.7 deg C and at reduced pressures of 0.1 and 0.2. It is shown that the Cooper correlation can predict the present pool boiling heat transfer data satisfactorily. In addition, a semi-analytical prediction method is proposed in the study; this semi-analytical model can not only predict the present data with success, but also give reasonably good accuracy with the experimental data from other researchers.

Details

  • Original title: Pool boiling of R22, R124 and R134a on a plain tube.
  • Record ID : 1998-0124
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 40 - n. 7
  • Publication date: 1997/05

Links


See other articles in this issue (2)