Replacement of R22 in heat pumps used for district heating.

Author(s) : GABRIELII C., VAMLING L.

Summary

In Swedish district heating systems several large (25 MW) turbo-compressor driven heat pumps using R22 are installed. The only commercially available alternative is R134a, but its use could decrease the heating capacity by 35%. The aim of the work is to find a mixture giving a better "economical performance" than R134a. The paper screens about 2000 mixtures, containing two or more of the components R134a, R32, R143a and R125.

Details

  • Original title: Replacement of R22 in heat pumps used for district heating.
  • Record ID : 2001-1535
  • Languages: English
  • Source: Proceedings of the 2000 International Refrigeration Conference at Purdue.
  • Publication date: 2000/07/25
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (52)