IIR document

Research of leakage characteristics of single screw refrigeration compressors with the Multicolumn Envelope Meshing Pair.

Author(s) : WANG Z., LIU Z., WU W., et al.

Type of article: Article, IJR article

Summary

The Multicolumn Envelope Meshing Pair (MEMP) was proposed and has been applied for the single screw refrigeration compressor (SSRC) to reduce the wear of the meshing pair. However, the geometric model shows its changed shape of the leakage paths compared with the existing straight line envelope meshing pair (LEMP). It is necessary to research the leakage characteristics of the SSRC with MEMP and LEMP, to evaluate the value of the proposed MEMP. In this paper, the geometric model of the leakage paths between star-wheel and screw rotor is established. A two-phase leakage mathematical model for gas-oil flow is presented to predict the gas leakage rate of the SSRC with MEMP. The experiments of the performance of a SSRC with MEMP were conducted to verify the leakage mathematical model. Obtained results show the leakage of the SSRC with MEMP is a little bit smaller than that of the SSRC with LEMP.

Available documents

Format PDF

Pages: 1-10

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Research of leakage characteristics of single screw refrigeration compressors with the Multicolumn Envelope Meshing Pair.
  • Record ID : 30012751
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 49
  • Publication date: 2015/01

Links


See other articles in this issue (18)
See the source