Simulation of a data center cooling system in emergency situation.

Simulace chladicího systému datacentra v havarijním stavu.

Author(s) : ZAVREL V., BARTÁK M., HENSEN J. L. M.

Type of article: Article

Summary

The paper deals with the simulation ot indoor environment in a data center at breakdown of its cooling system. Individual components of the cooling system during the breakdown were studied in detail with respect to their influence on the course of the emergency situation, in particular the influence of the cooling circuit thermal capacity. A complex numerical model was set up in TRNSYS simulation environment to predict energy flows and air temperatures in the data center. The simulation model describes in detail the cooling system including control elements and it takes into account heat accumulation in room constructions. The model represents a real data center and it was calibrated using data from a real emergency situation. The simulation results showed that the backup of water circuit makes possible to extend the operation time of the data center at emergency.

Available documents

Format PDF

Pages: 155-159

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Simulace chladicího systému datacentra v havarijním stavu.
  • Record ID : 30017452
  • Languages: Czech
  • Source: Vytápení Vetrání Instalace - vol. 24 - n. 4
  • Publication date: 2015/09