The performance evaluation of a room air conditioner using R32: in the case of cooling and heating mode.

[In Japanese. / En japonais.]

Author(s) : TAIRA S., YAZIMA R., KOYAMA S.

Type of article: Article

Summary

The test room air conditioner is a product developed for the R410A use. The COP, cooling and heating capacities, charge amount of refrigerant, electric power input, refrigerant thermodynamic states in the air conditioner etc. were measured for both refrigerant R410A and R32, based on JIS-C9612 standard. The experimental results of R32 are evaluated in comparison with the results of R410A, and the following points are confirmed: the performance of R32 is higher than R410A; the charge amount of R32 is less than that of R410A. The effects of the performance of components on the COP are also analyzed based on the measured thermodynamic states at both ends of components in the system. Then, it is clarified that the most effective factor is irreversibility of the compressor and the following is the pressure drop in low pressure side including the evaporator and the suction pipe in the system.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 2002-2822
  • Languages: Japanese
  • Source: Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 18 - n. 3
  • Publication date: 2001