Summary
Absorption cooling technologies converting excess heat and renewable heat resources to cooling energy have shown progress in recent years. In this study, two 400 kW LiBr solution absorption chiller types with series and parallel connected are analyzed over a range of parameter values to better understand their applicability for different uses. Thermodynamic models for the components were constructed and validated. The performance of the chillers related to heat transfer, energy, exergy, and economy performance was comprehensively analyzed. The operating performance was investigated by considering the external variables, including inlet cooling water, chilled water, and inlet steam temperatures and the solution allocation ratio. The results indicate that the parallel connected chiller reaches higher energy and exergy performance than the series-connected chiller, but the heat transfer and economic performance was lower. The coefficient of performance and the exergy efficiency of the parallel chiller were for the reference system 1.30 and 24.42%, respectively. Except for the exergy efficiency, the inlet steam and inlet chilled water temperature had positive impact on the heat transfer, energy, and economic performance, while the inlet cooling water temperature trends the opposite. The sensitivity analysis on solution allocation ratio showed that a higher ratio decreases the heat transfer and economic performance, but considering the energy and exergy performance, a suitable allocation ratio would be 0.54.
Available documents
Format PDF
Pages: 17 p.
Available
Free
Details
- Original title: Thermodynamic and economic performance assessment of double-effect absorption chiller systems with series and parallel connections.
- Record ID : 30031211
- Languages: English
- Subject: Technology
- Source: Energies - vol. 15 - n. 23
- Publishers: MDPI
- Publication date: 2022/12
- DOI: http://dx.doi.org/https://doi.org/10.3390/en15239105
Links
See other articles in this issue (18)
See the source
Indexing
-
Analysis of the ideal absorption cycle with ext...
- Author(s) : WIJEYSUNDERA N. E.
- Date : 1995/02
- Languages : English
- Source: Energy, Int. J. - vol. 20 - n. 2
View record
-
Performance optimization of an adsorption chill...
- Author(s) : SAPIENZA A., SANTAMARIA S., GLAZNEV I. S., et al.
- Date : 2011/04/06
- Languages : English
- Source: Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
View record
-
Performance of absorption refrigeration cycle a...
- Author(s) : CHEN J.
- Date : 1994/12
- Languages : English
- Source: Cryogenics - vol. 34 - n. 12
View record
-
A generalized model of a combined refrigeration...
- Author(s) : CHEN L., BI Y., SUN F., et al.
- Date : 1999/09
- Languages : English
- Source: Int. J. therm. Sci. - Rev. gén. Therm. - vol. 38 - n. 8
View record
-
A second law analysis and entropy generation mi...
- Author(s) : MYAT A., THU K., KIM Y. D., et al.
- Date : 2011/10
- Languages : English
- Source: Applied Thermal Engineering - vol. 31 - n. 14-15
View record