IIR document

Thermodynamic modelling and parameter determination of ejector for ejection refrigeration systems.

Author(s) : MA Z., BAO H., ROSKILLY A. P.

Type of article: Article, IJR article

Summary

This paper presents a detailed thermodynamic modelling method of an ejector for ejection refrigeration system. In this model, the primary flow in the ejector was assumed to fan out from the nozzle without mixing with the secondary flow in a certain downstream distance, so that a hypothetical throat was formed where the secondary flow reached the sound speed. However, the area of this hypothetical throat remained unknown. Therefore, based on several sets of experimental results, the present study developed empirical correlations of the hypothetical throat area to aid further modelling. The ratio of the hypothetical throat area to the mixing area was correlated with two dimensionless variables: one was the ratio of nozzle throat area to the mixing area, and the other one was the primary and secondary flow pressure ratio. The model has been validated by the measured primary mass flow rates and the critical back pressures.

Available documents

Format PDF

Pages: 117-128

Available

Free

Details

  • Original title: Thermodynamic modelling and parameter determination of ejector for ejection refrigeration systems.
  • Record ID : 30021908
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 75
  • Publication date: 2017/03
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2016.12.005

Links


See other articles in this issue (29)
See the source