IIR document

Thermodynamic performance of triple loop heat pump ventilation recovery system.

Number: pap. n. 473

Author(s) : MA A., MA G., WANG L., et al.

Summary

In order to improve the performance of the heat pump system under large temperature difference, this paper proposed a triple-loop heat pump ventilation recovery scheme, and an energy recovery performance test platform was set up based on the exhaust energy recovery of the building air-conditioning system. The performance of the single-loop and triple-loop heat pump systems were tested under different outdoor temperature conditions in winter and summer through experiments. The results showed that the overall performance of the triple-loop system was significantly higher than the single-loop under all operating conditions. Under winter conditions, the COP of the triple-loop system had reached to 11.19, when the indoor and outdoor temperature difference was 40 °C, and the COP of the triple-loop was 54.8% higher than the single-loop. Under summer conditions, the growth rate of the COP of the triple-loop system had reached to 89.8%, when the temperature difference was 13 °C, and the COP of the triple-loop was 74.6% higher than the single-loop.

Available documents

Format PDF

Pages: 7

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Thermodynamic performance of triple loop heat pump ventilation recovery system.
  • Record ID : 30026449
  • Languages: English
  • Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Publication date: 2019/08/24
  • DOI: http://dx.doi.org/10.18462/iir.icr.2019.0473

Links


See other articles from the proceedings (632)
See the conference proceedings