Summary
One of the main advantages of ice slurry as secondary refrigerant is the possibility of cold storage, which enables load shifting and peak shaving. During cold storage, ice crystals are subject to mechanisms such as attrition, agglomeration and Ostwald ripening causing changes in the crystal size distribution, which are of great importance for ice slurry systems since they influence other parameters such as pressure drop and heat transfer characteristics. Storage experiments with ice crystals in aqueous solutions of sodium chloride, ethylene glycol, ethanol and propylene glycol show that Ostwald ripening is the most important mechanism inducing an increase in average crystal size. The ripening rate strongly decreases as the solute concentration increases and the type of solute and the mixing regime also play an important role. The different ripening rates are caused by the fact that crystal growth and dissolution by means of Ostwald ripening are mainly limited by surface integration kinetics at low concentrations and by mass transfer at high solute concentrations.
Available documents
Format PDF
Pages: 27-36
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Time-dependent behaviour of different ice slurries during storage.
- Record ID : 2005-0663
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 28 - n. 1
- Publication date: 2005/01
Links
See other articles in this issue (12)
See the source
Indexing
-
Formulation of the latent heat of fusion of ice...
- Author(s) : KUMANO H., ASAOKA T., SAITO T., et al.
- Date : 2009/01
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 1
- Formats : PDF
View record
-
General properties and characteristics of aqueo...
- Author(s) : MELINDER Å.
- Date : 2008/09/07
- Languages : English
- Source: 8th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2008)
- Formats : PDF
View record
-
SECONDARY REFRIGERANTS FOR HEAT PUMP APPLICATIO...
- Author(s) : MELINDER Å.
- Date : 1985
- Languages : Swedish
- Source: Swed. Counc. Build. Res. - R114:1985; 104 p.; fig.
View record
-
Study on latent heat of fusion of ice in aqueou...
- Author(s) : KUMANO H., ASAOKA T., SAITO A., et al.
- Date : 2007/03
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 2
- Formats : PDF
View record
-
Study on effective latent heat of fusion of ice...
- Author(s) : ASAOKA T., KUMANO H., SAITO A., et al.
- Date : 2006/05/21
- Languages : English
- Source: ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
View record