Total energy consumption of water chiller and pump under different supply water temperatures.

[In Chinese. / En chinois.]

Author(s) : WANG G.

Type of article: Article

Summary

Establishes the calculation models of energy consumption of the water chiller and pump in fan-coil unit air conditioning chilled water system, and calculates the total energy consumption under different supply water temperatures. Under the calculation condition of this article, when the head of water pump is between 15 and 33.2 m, the chilled water supply temperature is 7°C and the supply-return water temperature difference is 5°C, the system energy consumption is the lowest; when the head of water pump is between 33.2 and 40 m, the chilled water supply temperature is 6°C and the supply-return water temperature difference is 6.17°C, the system energy consumption is the minimum.

Available documents

Format PDF

Pages: 96-98

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: [In Chinese. / En chinois.]
  • Record ID : 30008024
  • Languages: Chinese
  • Source: HV & AC - vol. 43 - n. 275
  • Publication date: 2013/03