IIR document

Zero gradient control for R-744 refrigeration cycles.

Author(s) : NOEDING M., TEGETHOFF W., KOEHLER J.

Type of article: Article, IJR article

Summary

This paper proposes a method called Zero Gradient Control, which is used to control the heat rejection pressure and the rotational speed of the fans of the gas cooler of R-744 refrigeration cycles nearly energy optimal. The basic concept is to develop algebraic terms for the partial derivatives of the COP with respect to the heat rejection pressure and the speed of the fans. These equations are evaluated online with measurement signals and directly fed to decentralized controllers with setpoint zero. The control structure is the same for both sub- and transcritical operation, requires little parameterization and can be applied to a wide range of systems. Using Zero Gradient Control, there is no need to calculate setpoints, which simplifies the mathematical effort in the implementation. Measurements for various scenarios validate the method even in the case of atypical system behavior or gas cooler fouling.

Available documents

Format PDF

Pages: 283-296

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Zero gradient control for R-744 refrigeration cycles.
  • Record ID : 30026832
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 106
  • Publication date: 2019/10
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2019.05.041

Links


See other articles in this issue (54)
See the source