IIR document

A study of accurate latent heat measurement for a PCM with a low melting temperature using T-history method.

Author(s) : PECK J. H., KIM J. J., KANG C., et al.

Type of article: Article, IJR article

Summary

When the latent heat of a phase change material (PCM) with a lower melting point than ambient temperature was assessed according to the standard T-history method using a vertically oriented test tube, a temperature gradient occurred in the longitudinal direction of the tube due to natural convection. This led to a decrease in the accuracy of the latent heat of fusion measurement. In this study, the accuracy of the measurement with the original T-history method was improved without decreasing the test's simplicity and convenience by setting the test tube horizontally. The heat transfer to the vapour-layer of the tube under volume change during melting was assumed to be negligible and the results were calculated using the two inflection points of temperature as the start and end of latent heat period. Under these assumptions, the results agree closely with other reference data. And, the new method proposed in this study showed a remarkable reduction in data scattering.

Available documents

Format PDF

Pages: 1225-1232

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: A study of accurate latent heat measurement for a PCM with a low melting temperature using T-history method.
  • Record ID : 2006-2189
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 29 - n. 7
  • Publication date: 2006/11

Links