A study on the performance of heat pump by mixing ratio of isobutane/propane mixed refrigerants.

Number: No 354

Author(s) : KANG G. H., NA S.-I., KIM M. S.

Summary

Natural refrigerants have global warming potential (GWP) and ozone depletion potential (ODP), but typical natural refrigerants have low COP, too. On the contrary, hydrocarbon refrigerants have high performance. In this study, using the characteristics of mixed refrigerants that can maintain a constant temperature difference during phase change, performance of the cycle according to the change in mixing ratio of isobutane and propane was calculated and measured. At outdoor temperature of 35°C and indoor temperature 27°C, COP of the cycle was maximized at isobutane ratio is near 0.8. 

Available documents

Format PDF

Pages: 5 p.

Available

Free

Details

  • Original title: A study on the performance of heat pump by mixing ratio of isobutane/propane mixed refrigerants.
  • Record ID : 30030123
  • Languages: English
  • Subject: Technology
  • Source: 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
  • Publication date: 2021/08/31

Links


See other articles from the proceedings (198)