Air conditioning system design for a supercomputing center.

[In Chinese. / En chinois.]

Author(s) : WU X.

Type of article: Article, Case study

Summary

Power density of this supercomputing center is extremely high, the single cabinet power reaches 20 kW, and the traditional data center cooling method cannot meet the demand. Adopts the row-level air conditioning cooling mode, sets the row-level air conditioning units directly on the middle rack, makes hot and cold aisle closed for each row of the front and back, and row-level air conditioning units as backup. Uses air-cooled units with natural cooling and the natural cooling function can automatically open in transition seasons and winter. Presents the air conditioning water system, outdoor air system, and smoke control and extraction system design.