AMMONIA-WATER TRIPLE-EFFECT ABSORPTION CYCLE.

Author(s) : DEVAULT R. C., MARSALA J.

Summary

AMONG THE BASIC TRIPLE-EFFECT CYCLES ONLY 1 PARTICULAR CYCLE IS ABLE TO USE AMMONIA-WATER. IT USES 2 CONDENSERS AND 2 ABSORBERS TO ACHIEVE THE < TRIPLE EFFECT >. CALCULATIONS ARE PRESENTED SHOWING THE RELATIVE PERFORMANCE OF A CONVENTIONAL DOUBLE-EFFECT CYCLE USING AMMONIA-WATER AND THE PERFORMANCE OF THIS TRIPLE-EFFECT CYCLE USING AMMONIA-WATER ON A COMPARABLE BASIS. THE TRIPLE-EFFECT CYCLE IS PREDICTED TO HAVE 18% HIGHER COOLING EFFICIENCY, LOWER PRESSURE, SIGNIFICANTLY REDUCED PUMPING POWER AND LOWER CONSTRUCTION COST.

Details

  • Original title: AMMONIA-WATER TRIPLE-EFFECT ABSORPTION CYCLE.
  • Record ID : 1991-1136
  • Languages: English
  • Publication date: 1990
  • Source: Source: ASHRAE Trans.
    vol. 96; n. 1; 676-682; 9 fig.; 1 tabl.; 14 ref.; append.; discuss.