IIR document

Condensation heat transfer and pressure drop in tubes with different aspect ratios.

Number: pap. ID: 184

Author(s) : KIM N. H., CHA S. J., BYUN H. W., et al.

Summary

In this study, condensation heat transfer coefficients of R410A were obtained in flattened tubes made from 5.0 mm inner diameter round tubes. The test range covered saturation temperature 45°C, heat flux 10 kW/m2K, mass flux 100-400 kg/m2s and quality 0.2-0.8. Results showed the effect of aspect ratio on condensation heat transfer coefficient was dependent on the flow pattern. For annular flow, the heat transfer coefficient increased as the aspect ratio increased. For stratified flow, however, the reverse was true. The pressure drop increased as aspect ratio increased. Existing correlations adequately predicted the heat transfer coefficients and pressure drops of the flattened tubes.

Available documents

Format PDF

Pages: 8 p.

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Condensation heat transfer and pressure drop in tubes with different aspect ratios.
  • Record ID : 30001611
  • Languages: English
  • Source: Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
  • Publication date: 2011/08/21

Links


See other articles from the proceedings (569)
See the conference proceedings