Condensation of R134a on horizontal integral-fin titanium tubes.
Author(s) : FERNÁNDEZ-SEARA J., UHÍA F. J., DIZ R., et al.
Type of article: Article
Summary
Experimental research was conducted to evaluate the condensation of R134a on horizontal smooth and integral-fin (32 fpi) titanium tubes of 19.05 mm outer diameter. Experiments were carried out at saturation temperatures of 30, 40 and 50°C and wall subcoolings from 0.5 to 9°C. The results show that the condensation heat transfer coefficients (HTCs) on the smooth tubes are well predicted by the Nusselt theory with an average error of +2.38% and within a deviation between +0.13 and +5.42%. The enhancement factors provided by the integral-fin tubes on the overall condensation HTCs range between 3.09-3.94, 3.27-4 and 3.54-4.1 for the condensation temperatures of 30, 40 and 50°C, respectively. The enhancement factors increase by increasing the wall subcooling and with the rise of the condensing temperature. The condensate flooded fraction of the integral-fin tubes perimeter varies from 25 to 20% at saturation temperatures of 30 and 50°C, respectively. The correlation reported by Kang et al. (2007) predicted the experimental data with a mean deviation of -5.5%. [Reprinted with permission from Elsevier. Copyright, 2009].
Details
- Original title: Condensation of R134a on horizontal integral-fin titanium tubes.
- Record ID : 2011-0084
- Languages: English
- Source: Applied Thermal Engineering - vol. 30 - n. 4
- Publication date: 2010/04
- DOI: http://dx.doi.org/10.1016/j.applthermaleng.2009.09.007
Links
See other articles in this issue (4)
See the source
-
Experimental investigations on condensation cha...
- Author(s) : KUKREJA R., JAIN S., AGARWAL R. S.
- Date : 2011/08/21
- Languages : English
- Source: Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Formats : PDF
View record
-
Experimental investigation on flow boiling heat...
- Author(s) : SHAO L., HAN J., CHEN C., et al.
- Date : 2009/12
- Languages : Chinese
- Source: Journal of Refrigeration - vol. 30 - n. 6
- Formats : PDF
View record
-
EFFECT OF FIN SPACING ON THE PERFORMANCE OF HOR...
- Author(s) : YAU K. K., COOPER J. R., ROSE J. W.
- Date : 1985/05
- Languages : English
- Source: J. Heat Transf. - vol. 107 - n. 2
View record
-
An experimental comparison of the refrigerant f...
- Author(s) : ZAREH M., JAVIDMAND P., HOFFMANN K. A.
- Date : 2014/07/14
- Languages : English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Condensation characteristics of R134A and R404A...
- Author(s) : KUKREJA R., SINGH S.
- Date : 2019/08/24
- Languages : English
- Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
View record