Summary

The condensation heat transfer of oilrefrigerant mixtures on the outside of horizontal, copper tubes was experimentally investigated. A test apparatus was designed and constructed to condense oil-refrigerant mixtures. The apparatus used s constant pressure boiling and condensing system with oil sprayed into the condensing refrigerant vapour over the test surface. Experimentally measured values of the condensing heat transfer coefficients were measured for various oil concentrations, test surfaces and operating conditions. The condensation of pure refrigerant on the smooth test surface was in agreement with the predicted results and previous experimentally measured values. At oil concentrations of 6-7%, the effect of the oil became greater than predicted.

Available documents

Format PDF

Pages: 209-222

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Condensation of refrigerant-oil mixtures on horizontal tubes.
  • Record ID : 30000946
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 4 - n. 4
  • Publication date: 1981/07