Control of dry expansion evaporators with zeotropic blends.

Regulering af tørfordampere med zeotrope kølemidler.

Author(s) : SCHMIDT F.

Summary

Zeotropic blends change temperature during evaporation (glide). The composition can alter following a leakage, and the evaporation temperature can increase. This increase is negligible (less than 1 deg C) for R502 substitutes but must be compensated when using R12 and R22 substitutes where the glide is around 3 deg C. The paper explains how adjustments could be done using different electronic expansion valve types.

Details

  • Original title: Regulering af tørfordampere med zeotrope kølemidler.
  • Record ID : 1998-2867
  • Languages: Danish
  • Source: Dansk koledag '95.
  • Publication date: 1995/03/09
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (4)
See the conference proceedings