CORRELATION FOR EVALUATION OF THE PERFORMANCE CHARACTERISTICS OF VAPOUR ABSORPTION REFRIGERATION CYCLES.

Author(s) : ASHA IYER P. S., SRINIVASA MURTHY S., KRISHNA MURTHY M. V.

Type of article: Article

Summary

FOUR CYCLES ARE STUDIED: A CONVENTIONAL ONE-STAGE CYCLE WITH 2 PRESSURES CORRESPONDING TO THE CONDENSER AND EVAPORATOR TEMPERATURES ; A CYCLE WITH 3 LEVELS OF PRESSURE AND A GENERATOR FUNCTIONING AT A PRESSURE SUPERIOR TO THE ONE OF THE CONDENSER ; A TWO-STAGE CYCLE WITH A RESORBER/DESORBER LOCATED BETWEEN THE EVAPORATOR AND THE ABSORBER IN A CONVENTIONAL ONE-STAGE CYCLE AND A DOUBLE EFFECT CYCLE, WITH 2 GENERATORS. THE WORKING FLUID PAIRS USED ARE R21-DMF, R22-DMF, R22-DMETEG, AMMONIA-SODIUM THIOCYANATE AND WATER-LITHIUM BROMIDE. THE COP AND THE HEAT QUANTITIES AT THE GENERATOR INLET AND AT THE ABSORBER AND CONDENSER OUTLET ARE CORRELATED WITH THE OPERATION TEMPERATURES. (Bibliogr. int. IFP-AFME-CNRS, FR., 89-230-1320.

Details

  • Original title: CORRELATION FOR EVALUATION OF THE PERFORMANCE CHARACTERISTICS OF VAPOUR ABSORPTION REFRIGERATION CYCLES.
  • Record ID : 1990-0118
  • Languages: English
  • Source: Sol. Wind Technol. - vol. 5 - n. 2
  • Publication date: 1988
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (1)
See the source