DYNAMIC CHARACTERISTICS OF AN AIR CONDITIONED ROOM WITH HIGH SIDEWALL OUTLET.
Author(s) : BHATTACHARYYA P. C.
Type of article: Article
Summary
THE DYNAMIC CHARACTERISTICS OF AN AIR CONDITIONED ROOM HAVE BEEN STUDIED USING A SMALL SCALE MODEL ROOM. USING THE PULSE TESTING TECHNIQUE, AN INPUT-OUTPUT DESCRIPTION OF THE ROOM PROCESS IN THE LAPLACE DOMAIN WAS OBTAINED BETWEEN THE SUPPLY AND RETURN AIR TEMPERATURES. FOR AROOM HAVING A HIGH SIDEWALL OUTLET, THE ROOM PROCESS WAS THUS DESCRIBED BY A TRANSFER FUNCTION RELATING THE SUPPLY AND RETURN AIR TEMPERATURES. WITHIN THE EXPERIMENTAL RANGE THIS TRANSFER FUNCTION WAS FOUND TO CONTAIN A FIRST ORDER LEAD AND A THIRD ORDER LAG COMPONENT ALONG WITH A TRANSPORTATION DELAY AND A STEADY STATE GAIN VALUE OF LESS THAN UNITY.
Details
- Original title: DYNAMIC CHARACTERISTICS OF AN AIR CONDITIONED ROOM WITH HIGH SIDEWALL OUTLET.
- Record ID : 1984-2411
- Languages: English
- Source: Build. Environ. - vol. 18 - n. 4
- Publication date: 1983
Links
See other articles in this issue (1)
See the source
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Climatic chamber; Measurement; Testing; Air conditioning