Economic and Technical Analysis of a Hybrid Dry Cooling Cycle to Replace Conventional Wet Cooling Towers for High Process Cooling Loads.
Author(s) : TAIMOOR A. A., SAEED U., RATHER S-U., AL-SHAHRANI S., BAMUFLEH H. S., ALHUMADE H., SULAIMON A. A., ALALAYAH W. M., SHARIFF A. M.
Type of article: Periodical article
Summary
Scarcity has made fresh water too economically and socially too valuable to be used by the processing industry without restriction. Wet evaporative cooling cycles offer competitive advantages in terms of CoP compared to other cooling cycles with relatively low cost but requiring extensive quantities of water. Dry cooling, on the other hand, requires large heat-transfer areas, in addition to high power requirements. In this study, a hybrid cycle is proposed for high-end cooling loads of 215 MW. The proposed cycle combines the benefits of phase change to make dry cycles competitive. Furthermore, the proposed cycle also diminishes the extensive use of various chemicals used in wet cooling cycles. The applicable dry bulb temperature range is 25–50 °C. Variations in cooling fluid cold temperature due to ambient conditions are curtailed to a maximum of 2 °C by the proposed cycle. A technoeconomic comparison of the proposed solution to wet evaporative cooling is presented, and the effects are summarized without providing extensive design calculations. ASPEN modules are used design and simulation.
Available documents
Format PDF
Pages: 17 p.
Available
Free
Details
- Original title: Economic and Technical Analysis of a Hybrid Dry Cooling Cycle to Replace Conventional Wet Cooling Towers for High Process Cooling Loads.
- Record ID : 30030878
- Languages: English
- Subject: Technology
- Source: Energies - vol. 15 - n. 21
- Publishers: MDPI
- Publication date: 2022/11
- DOI: http://dx.doi.org/10.3390/en15217986
Links
See other articles in this issue (29)
See the source
Indexing
-
Themes:
Ejector systems, air cycle, Stirling cycle, other cycles);
Evaporators, condensers and other heat exchangers - Keywords: Cooling tower; Cost; Hybrid system; Thermodynamic cycle; Evaporative system; Wet bulb temperature; Simulation; Industrial application; Heat exchanger; Fresh water; COP; Design
-
Effect of heat rejection load and wet bulb on c...
- Author(s) : SCHWEDLER M.
- Date : 2014/01
- Languages : English
- Source: ASHRAE Journal - vol. 56 - n. 1
View record
-
Experimental study of a novel non-packing close...
- Author(s) : TU A., LIU S., MO X., CHEN E., ZHAN X., ZHU D.
- Date : 2022/12
- Languages : English
- Source: Energies - vol. 15 - n. 24
- Formats : PDF
View record
-
Wet bulb temperature: the misunderstood element.
- Author(s) : BURGER R.
- Date : 1993/09
- Languages : English
- Source: Heat. Pip. Air Cond. - vol. 65 - n. 9
View record
-
A study on an optimal approach temperature cont...
- Author(s) : LIU C. W., CHUAH Y. K.
- Date : 2011/05
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 3
- Formats : PDF
View record
-
Energy efficiency control strategy for air cond...
- Author(s) : YANG L., LU J., TANG H., et al.
- Date : 2013/04
- Languages : Chinese
- Source: HV & AC - vol. 43 - n. 276
- Formats : PDF
View record