IIR document

Effect of oil on R134a distribution in the microchannel heat exchanger with vertical header.

Author(s) : ZOU Y., HRNJAK P. S.

Type of article: Article, IJR article

Summary

This paper presents refrigerant R134a and oil (PAG 46) mixture upward flow in the vertical header of microchannel heat exchanger (compared to pure R134a and R410A), and its effect on distribution. The mixture enters into the header through the five tubes in the bottom pass and exits through the five tubes in the top pass representing the flow in the heat pump mode of outdoor heat exchangers in reversible systems. The quality was varied from 0.2 to 0.8 and the mass flow rate from 1.5 to 4.5 kg h-1 per tube. The oil circulation rate (OCR) was varied from 0% to 4.7%. It was found that at low OCR, e.g. 0.5%, the distribution was worse than pure R134a, whereas at high OCR, the distribution was improved and better than pure R134a in some cases. This was due to sufficient oil would create a lot of foams and enlarge the liquid region in the header based on the visualization.

Available documents

Format PDF

Pages: 201-210

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Effect of oil on R134a distribution in the microchannel heat exchanger with vertical header.
  • Record ID : 30010715
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 40
  • Publication date: 2014/04

Links


See other articles in this issue (41)
See the source