ENERGY SAVING, CAPACITY CONTROL FOR HEAT PUMPS.

Author(s) : FORDSMAND M.

Summary

BOTH CALCULATION AND PRACTICAL MEASUREMENTS VERIFY THE ENERGY SAVING PROPERTIES. IT IS BASED ON THE FACT, THAT THE TEMPERATURE DIFFERENCES IN THE HEAT EXCHANGERS ARE KEPT RATHER CONSTANT, WHEN THE ON AND OFF PERIODS FOR THE COMPRESSOR ARE SUFFICIENTLY SHORT. WITH CONSTANT WATER TEMPERATURES THIS WILL RESULT IN MORE FAVORABLE PRESSURE CONDITIONS FOR THE COMPRESSOR AND THE COP WILL RISE WITH DECREASE IN THE CAPACITY. THE BEST COP WILL BE OBTAINED WITH SMALL PRESSURE RATIO, SMALL RELATIVE HEAT OUTPUT, WITH TIMEBASIS AROUND 15-60 SECONDS, AND WHEN THE HEAT EXCHANGERS ARE UNDERDIMENSIONED.

Available documents

Format PDF

Pages: 342-346

This document is to be digitised and will be available within 10 working days

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: ENERGY SAVING, CAPACITY CONTROL FOR HEAT PUMPS.
  • Record ID : 1988-1611
  • Languages: English
  • Source: Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.
  • Publication date: 1987/08/24
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (509)
See the conference proceedings