IIR document
Energy saving performance of the wet-air-conditioning system.
Number: pap. n. 461
Author(s) : TATEIWA K., MURASAWA I., WATANABE T.
Summary
Stable temperature and humidity of the indoor air are required in many fields, such as the electronic devices factory, laboratory, paint booth, and metal processing booth. But it is difficult to keep stable temperature and humidity of supply air using general air-conditioning system that is composed of blower, heating and cooling coil, and vaporizing humidifier.
The wet-air-conditioning system that has direct contact unit of air and water is effective to resolve this problem. This system has been found to be able to not only maintain stable temperature and humidity of supply air but also contribute to saving energy because of two reasons.
First, it is possible to reduce cooling heat because this system can provide evaporative cooling heat as a result of direct contact of supply air with chilled water. Estimated cooling energy reduction of this system is from 20% to 30%, while that of general system is about 10% throughout the year. This estimate was almost accurate in the operation of the actual office building.
Second, it is possible to reduce the hot water temperature because this system humidifies the supply-air before heating. By reducing the hot water temperature, it is possible to improve the efficiency of the heat source system.
Available documents
Format PDF
Pages: 7 p.
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Energy saving performance of the wet-air-conditioning system.
- Record ID : 30015892
- Languages: English
- Source: Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Publication date: 2015/08/16
- DOI: http://dx.doi.org/10.18462/iir.icr.2015.0461
Links
See other articles from the proceedings (657)
See the conference proceedings
Indexing
-
Kako smanjiti potrebe za energijom za hladenje ...
- Author(s) : PAUL J.
- Date : 2008/12/03
- Languages : Serbian
- Source: Zbornik radova. 39. Medunarodni kongres o grejanju, hladenju i klimatizaciji.
- Formats : PDF
View record
-
Efficienza a carico parziale nei sistemi split:...
- Author(s) : JOPPOLO C. M., MIGLIOLI S., MAGNI F., et al.
- Date : 2004/03/03
- Languages : Italian
- Source: Impianti, edifici, città: integrazione e nuove visioni di progetto e di gestione. 44e Convegno Internazionale AICARR [CD-ROM]./ HVAC&R systems, envelope and urban context: integration and new vision of design and operation. 44th International conference of AICARR [CD-ROM].
View record
-
Air conditioning with ammonia.
- Author(s) : TOTH S. J.
- Date : 1994/03/06
- Languages : English
- Source: Ammonia: the right stuff.
View record
-
Part-load performance of on-off air-cooled chil...
- Author(s) : BENSAFI A., GAILLARD N., MORIN J. M.
- Date : 2007/08/21
- Languages : English
- Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
View record
-
Hibridno hladenje kontejnera za telekomunikacio...
- Author(s) : ZAKULA T., BALEN I., ŠIMIC I.
- Date : 2014/12/03
- Languages : English
- Source: Zbornik radova. 45. Medunarodnikongres i izložba o grejanju hladenju i klimatizaciji./ Proceedings. 45th International congress and exhibition on heating, refrigeration and air conditioning (HVAC&R).
- Formats : PDF