EXPERIENCE WITH A 450 KILOWATT INDUSTRIAL HEAT PUMP FOR COMBINED SPACE AND PROCESS HEATING.

Author(s) : COLDING L.

Summary

THE AUTHOR PRESENTS A PLANT WITH A COMPRESSION SYSTEM, OF A NOMINAL CAPACITY OF 450 KILOW AT 291/338 K (18/65 DEG C). THE ENERGY IS DRAWN FROM THE WASTE HEAT OF THE CONDENSER OF AN AMMONIA REFRIGERATION PLANT. THE HIGH TEMPERATURE HEAT IS EXCHANGED IN THREE CONDENSERS: FOR HEATING BUILDINGS, WATER AND A CLEANING MACHINE FOR TRANSPORT BOXES. THE AVERAGE COP IN A 27 DAY PERIOD IS 2.9 AND MAXIMUM COP IS 3.85.

Available documents

Format PDF

Pages: 553-559

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: EXPERIENCE WITH A 450 KILOWATT INDUSTRIAL HEAT PUMP FOR COMBINED SPACE AND PROCESS HEATING.
  • Record ID : 1986-0836
  • Languages: English
  • Source: [Refrigeration serving humanity]. Proceedings of the XVIth international Congress of Refrigeration.
  • Publication date: 1983/08/07