IIR document

Experimental evaluation of the use of homogeneous and slip-flow two-phase dynamic models in evaporator modelling.

Summary

Distributed dynamic models of a simple coaxial-type evaporator were used in the simulation tool Sinda/Fluint. In order to obtain data for model validation, an experimental set-up was established. Model validation showed that the dynamic response of the homogeneous model was too fast whereas the results based on the slip-flow model agreed very well. Another difference in the results from the two types of model was the estimation of charge. The overall conclusion is that to investigate the dynamic behaviour of the refrigerant in the evaporator, it is necessary to use a slip-flow two-phase model instead a homogeneous one.

Available documents

Format PDF

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental evaluation of the use of homogeneous and slip-flow two-phase dynamic models in evaporator modelling.
  • Record ID : 2000-1245
  • Languages: English
  • Source: 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Publication date: 1999/09/19

Links


See other articles from the proceedings (447)