Experimental study on replacement of R22 with R417A in heat pump heating water system.

[In Chinese. / En chinois.]

Author(s) : LI X., YAN Z.

Type of article: Article

Summary

In the heat pump heating system, the theoretical cycle analysis and a drop in experimental investigation on the performance of new fluid R417A as substitute of R22 were carried out. The results show that heating output of R417A is slightly less, but its power consumption decreases by about 10.58%, and COP is higher than that of R22. The discharge temperature of R417A is lower than that of R22. The system with R417A operates in a normal way and its lubricant does not need to be changed.

Available documents

Format PDF

Pages: 1-4

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: [In Chinese. / En chinois.]
  • Record ID : 2005-2806
  • Languages: Chinese
  • Source: Journal of Refrigeration - n. 4
  • Publication date: 2003