Summary
R32 is a potential alternative refrigerant for its environmental protection capability and thermal performance. But the slight flammability limits its application. Therefore, safety analysis is needed. This paper studied the influence of different leakage locations and rates on the indoor R32 distribution with air conditioner operating, and obtained the R32 leakage and diffusion characteristics. It showed that the leakage at the evaporator of indoor unit can be divided into two processes, fast leakage stage and slow. Outlet leakage of the evaporator is more dangerous than the inlet. And only large leakage flow in evaporator outlet can
cause high R32 concentration near the indoor unit, reaching 16.79% , which exceeds the lower flammable limit (14.4%) 16.6%. If flammable concentration exists for 22 s, the fire probability exists but it's low. Air exhausting can decrease the concentration of indoor R32 effectively.
Available documents
Format PDF
Pages: 10-16
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: [In Chinese. / En chinois.]
- Record ID : 30019680
- Languages: Chinese
- Source: Journal of Refrigeration - vol. 36 - n. 166
- Publication date: 2015/12
- DOI: http://dx.doi.org/10.3969/j.issn.0253-4339.2015.06.010
Links
See other articles in this issue (5)
See the source
Indexing
- Themes: HFCs
- Keywords: Split system; Air conditioner; R32; Performance; Expérimentation; Evaporator; Leakage; Refrigerant; Diffusion
-
Simulation of leakage of mildly flammable refri...
- Author(s) : OKAMOTO H., HATTORI T., DANG C., et al.
- Date : 2014/07/14
- Languages : English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
The safety measures of the mini-split air-condi...
- Author(s) : TAKAICHI K.
- Date : 2013/11
- Languages : Japanese
- Source: Refrigeration - vol. 88 - n. 1033
View record
-
Effects of refrigerant lubricant combinations o...
- Author(s) : BENANTI T., URREGO R., HESSELL E., et al.
- Date : 2014/07/14
- Languages : English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Drop-in testing of R32 blends as R22 alternativ...
- Author(s) : KONDEPUDI S. N.
- Date : 1993
- Languages : English
- Source: ASHRAE Transactions.
View record
-
Refrigerant and lubricant mass distribution in ...
- Author(s) : WUJEK S. S., BOWERS C. D., POWELL J. W., et al.
- Date : 2014/07/14
- Languages : English
- Source: 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF