Summary
The test set-up is composed of compressor, condenser, expansion valves, two evaporators, and ejector which is installed between two evaporators. When the external conditions are fixed, results show that COP increases as the inlet temperature of the other evaporator becomes higher. It is also shown that the COP decreases as entrainment ratio of the ejector increases. For the same conditions, the COP of dual-evaporator refrigeration system with an ejector is superior to that of the single-evaporator vapour compression system by 3 to 6%.
Details
- Original title: Experimental study on the performance of dual-evaporator refrigeration system with an ejector.
- Record ID : 2001-1371
- Languages: English
- Source: Proceedings of the 2000 International Refrigeration Conference at Purdue.
- Publication date: 2000/07/25
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles from the proceedings (52)
See the conference proceedings
-
Experimental investigation of an alternating ev...
- Author(s) : LAVANIS M., HAIDER I., RADERMACHER R.
- Date : 1998
- Languages : English
- Source: ASHRAE Transactions. 1998 annual Meeting, Toronto, Ontario + CD-ROM.
View record
-
Refrigerator with 2-stage parallel refrigeratio...
- Author(s) : NOGUCHI A.
- Date : 2004
- Languages : Japanese
- Source: Refrigeration - vol. 79 - n. 924
View record
-
Application of Tandem System to high-efficiency...
- Author(s) : KIM K., KOPKO B., RADERMACHER R.
- Date : 1995/06/24
- Languages : English
- Source: ASHRAE Transactions.
View record
-
Method for evaluating the efficiency of the air...
- Author(s) : PAL'TI A. M., VEKSLER E. M.
- Date : 1991
- Languages : Russian
- Source: Kholodilnaya Tekhnika - n. 12
View record
-
HEAT EXCHANGE PROBLEMS AND THE SHAPE OF WIRE CO...
- Author(s) : DEKA A., KULESZA J.
- Date : 1988
- Languages : Polish
- Source: Chlodnictwo - vol. 23 - n. 1
View record