Field monitoring of ground-coupled heat pump systems for heating and cooling supply of nonresidential buildings: analysis of energy and efficiency performance.

Felduntersuchung von erdgekoppelten Wärmepumpen für die Wärme- und Kälteversorgung von Nichtwohngebäuden : Analyse der Energie- und Effizienzperformance.

Author(s) : KALZ D., WINIGER S., SONNTAG M., et al.

Type of article: Article

Summary

The energy and efficiency performance of 16 large heat pump systems was assessed in detail based on multi-annual measurement campaigns. For the heat pump systems, seasonal performance factors from 2.3 to 6.1 kWhtherm/kWhel have been achieved. The use of ground-coupled reversible heat pumps for cooling is also an efficient and sustainable approach to cooling building. Here, the relativity high supply water temperatures of 16 to 20°C allow for cooling with good energy efficiencies.

Details

  • Original title: Felduntersuchung von erdgekoppelten Wärmepumpen für die Wärme- und Kälteversorgung von Nichtwohngebäuden : Analyse der Energie- und Effizienzperformance.
  • Record ID : 30014021
  • Languages: German
  • Source: KI Kälte Luft Klimatechnik - n. 12
  • Publication date: 2014/12

Links


See other articles in this issue (5)